'Temperature control application
'using SCB-48206 RTD interface board
'connected to RIO-47120
'************************************
#tcntrl
AQ 0,3; 'set analog input to 0-5
DQ 0,4; 'set analog out to +/-10
'.012 deg/V conversion for RTD
'20degC is desired temperature
setpt= .012*20+2;'desired setpoint  
CL 1000;  'loop update rate of 1sec
AF 0;  'analog in 0 as feedback
AZ 0;  'analog out 0 as control Voltage
KP 25;  'set PID filter values
KD 50
KI 0
DB .024;  '2 deg deadband
PS setpt;  'pass setpt variable to PS
EN